Si71-812
Inspection and Maintenance of the Humidifier
Maintenance
43
2.2
Replacing the Humidifier Element
Replacing the
Humidifier
Element
<VKM-GAMV1
series only>
The humidifier element needs to be replaced regularly.
The humidifier element should in general be replaced once every three years when supply
water is soft water, but outside factors (water quality, hard water, etc.) as well as operating
conditions (24-hour-a-day air conditioning, etc.) may shorten its productive life.
Contact your dealer if you have any questions.
Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of
hardness : 150mg/l.
(Life of humidifying element is about 1 year (1,500 hours), under the supply water conditions of
hardness : 400mg/l.)
Annual operating hours : 10 hours/day × 26 days / month × 5 month = 1,300 hours.
Contact your dealer for details.
Note : Breakage due to taking apart or cleaning inside by anyone other than our authorized
dealers may not be included in the warranty.