Troubleshooting
Si71-812
68
Troubleshooting
2.13
Dedicated LCD Remote Controller
Error Detection
Method
When “
88
” remains on remote controller display.
Error Generating
Conditions
Possible Causes
Master-slave setting of remote controller
Remote controller PC board assembly error
Main unit PC board assembly error
Troubleshooting
Dedicated Remote Controller
Main Unit PC board (A1P)
Check to see if master-
slave remote controller is
used.
Check microcomputer
operation monitor on
main unit PC board.
Is it flashing?
YES
YES
Change master-slave selection
switch to set proper master-
slave relation.
One should be set to Master,
and the other set to Slave.
Replace remote controller.
Replace main unit PC board.
Is
master-slave
remote controller
used?
(HF007)
NO
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Master-slave
selection switch
Remote controller
PC board assembly
(HL030)
HAP
(HL031)
(Microcomputor Operation Monitor)
Summary of Contents for VKM100GAMV1
Page 9: ...Introduction Si71 812 viii ...
Page 43: ...Operation Si71 812 34 Operation ...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Page 103: ...Piping Diagram Si71 812 94 Appendix ...
Page 105: ...Si71 812 ii Index ...