Troubleshooting
Si71-812
76
Troubleshooting
2.20
“
UE
”
Malfunction of Transmission between Central
Remote Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
All models of indoor units
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and central remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor unit
Connector for setting master controller is disconnected.
Failure of PC board for central remote controller
Defect of indoor unit PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
power supply turned
on for indoor units displaying
malfunction?
Is
transmission wiring
disconnected or wired
incorrectly?
Is the
transmission wiring
with the master controller
disconnected or wired
incorrectly?
Is the
master controller's
connector for setting
master controller
disconnected?
Set the group No. correctly.
Replace indoor unit PC
board.
Fix the wiring correctly.
Fix the wiring correctly.
Connect the connector
correctly.
Replace the central PC board.
Reset power supply
simultaneously for all optional
controllers for centralized
control.
YES
YES
NO
YES
YES
YES
YES
Turn indoor unit's power
supply.
YES
NO
NO
NO
NO
NO
NO
Has
an indoor unit once
connected been remove
or its address
changed?
Is the group
No. of malfunctioning
indoor units set?
Is transmission
with all indoor units
malfunctioning?
(V2832)
Summary of Contents for VKM100GAMV1
Page 9: ...Introduction Si71 812 viii ...
Page 43: ...Operation Si71 812 34 Operation ...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Page 103: ...Piping Diagram Si71 812 94 Appendix ...
Page 105: ...Si71 812 ii Index ...