Si71-812
Operation
Opration
15
1.2
Features of VKM-GA(M)
Basic control of VKM
VKM sucks the air after OA has subjected to total heat exchange with RA, detects the air temperature by
means of the thermistor for inlet air into DX-coil (R3T) to make a judgment on operation mode, cooling or
heating and exercises the control on the capacity of air heat exchanger.
Sensor position and its function
VKM consists of indoor unit + total heat exchanger portion.
Dissimilarities with normal indoor unit are :
- Position of thermostat in the normal indoor unit : Position to detect RA temperature
- Position of thermostat in VKM : Position to detect the air subjected to total heat
exchange between OA and RA.
Therefore, the temperature detected by VKM gets lower than that of the indoor unit thermostat.
Doing so allows VKM to perform treatment of outside air with stability even as the indoor unit stays thermo-
OFF state because of big difference between the set temperature and suction temperature even though the
set temperature of VKM and indoor unit are the same.
Because VKM-GA(M) model is equipped with a heat exchanger unit, a PC-board (corresponding to VRV air
conditioner’s PC-board) for controlling the heat exchanger has been built-in in addition to a PC-board for
ventilation. These two PC-boards are connected via remote controller line (P1, P2) to perform an
interlocked control. Its control system provides the same condition when 1 ventilation and 1 VRV air
conditioner have been remotely controlled. No air-conditioning (temperature controlling) function has been
equipped. Therefore, it is necessary to prepare separately an indoor unit for air-conditioning purpose.
Humidifier
Total heat
exchanger
element
DX-Coil
electlic
expantion
valve
Divert the module of indoor unit
Divert the module of total heat exchanger
Thermistor for
liquid line
temperature
R4T
R5T
R3T
Thermistor for
gas line temperature
R1T
Thermistor for
indoor air
R2T
Thermistor for
outdoor air
RA
SA
OA
EA
Thermistor or inlet air into DX-coil (R3T)
-
This thermistor exercises the control on the capacity of
heat exchanger by means of electlic expantion valve in
accordance with the difference between detected
temperature and set temperature.
-
In the case of automatic mode, judgment on operation
mode, cooling or heating is made based on the detected
temperature.
Element of
total heat
exchanger
Heat
exchanger
unit
PC-board for ventilation
P1,P2
P1,P2
Corresponding multiple
type for building PC-board
Equivalent
BRC1A62
(BRC1D527)
remote controller
for air-conditioner
A group of 1 ventilation/1 multiple type for VRV indoor unit
An image sketch of VKM-GA(M)
Summary of Contents for VKM100GAMV1
Page 9: ...Introduction Si71 812 viii ...
Page 43: ...Operation Si71 812 34 Operation ...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Page 103: ...Piping Diagram Si71 812 94 Appendix ...
Page 105: ...Si71 812 ii Index ...