Operation
Si71-812
28
Operation
Press the on/off button.
The operation lamp lights up and the system starts operation.
Stopping the system
Press start/stop one more time. The operation lamp will go off. The unit will stop.
•
After stopping operation, the fan may continue operating for up to a minute.
•
The fan may stop, but this is not a malfunction.
Note
•
Do not turn off the power immediately after operation stops. Wait at least 5 minutes.
Not waiting may cause leaking or malfunction.
•
Do not change operations suddenly.
It can result not only in malfunction but also failure of switches or relays in the remote controller.
•
Never press the button of the remote controller with a hard, pointed object.
The remote controller may be damaged.
EXPLANATION OF OPERATION MODE
Note
•
This unit cannot control room temperature. If this is needed, do not install the HRV unit alone, but rather
install another indoor unit.
EXPLANATION OF VENTILATION MODE
Note
•
These icons below are displayed on the remote controller BRC1D527.
Automatic mode
: When combined with a VRV system air conditioner
The unit automatically switches between “
” and “
” based on information
from the VRV system air conditioner (heating, cooling, fan, and set temperature) and
information from the HRV unit (indoor and outdoor temperatures).
The unit automatically switches between “
” and “
” when it is combined with
an air conditioner (Not produced by Daikin) and based on only the information from
the HRV unit (indoor and outdoor temperatures) when the HRV unit is operating
alone.
Total heat exchange mode
: Outdoor air passes through the heat exchange element and heat
exchanged air is sent into the room.
Bypass mode
: In this mode outdoor air does not through the heat exchange element, but rather sent
into the room as is.
EXPLANATION OF HEATING OPERATION
Defrost operation
•
In heating operation, freezing of the outdoor unit coil increases. Heating capability decreases and the
system goes into defrost operation.
•
The remote controller will read “
” until the hot air starts blowing.
•
It returns to the heating operation again after 6 to 8 minutes (10 at the longest).
•
During defrost operation, the fans of the unit continues driving (factory setting).
The purpose of this is to maintain the amount of ventilation and humidifying.
•
The change of the layout in the room should be examined when the cold draft from air supplying
opening is feared.
•
Though the fan can be stopped by the setting of remote controller.
Do not stop the fan in the place where no ventilation by stopping the fan may cause the influence of
diffusion of air which it is dirty and moisture into another room, or the inflow from outside the room.
(outflow such as viruses from the sickroom, or smell leakage from the rest room, etc.)
Contact your dealer for details.
Hot start
•
The remote controller will read “
” until the hot air starts blowing, e.g. at the start of heating
operation.
Cooling mode
Heating mode
Automatic mode
It automatically selects “
” or “
.”
Fan mode
It only operates in ventilation mode.
The unit processes outside air using the heat
exchanger element, but not the DX expansion coil.
While operating in ventilation mode, the
unit adjusts the outside air to the indoor
temperature and then brings it into the
room.
4
Summary of Contents for VKM100GAMV1
Page 9: ...Introduction Si71 812 viii ...
Page 43: ...Operation Si71 812 34 Operation ...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Page 103: ...Piping Diagram Si71 812 94 Appendix ...
Page 105: ...Si71 812 ii Index ...