Maintenance
Si71-812
38
Maintenance
1.2
Maintenance for the
Heat Exchange Element
CLEANING FREQUENCY
AT LEAST ONCE EVERY TWO YEARS (FOR GENERAL OFFICE USE)
(CLEAN THE ELEMENT MORE FREQUENTLY IF NECESSARY.)
1. Use a vacuum cleaner to remove dust and foreign objects on the surface of the heat
exchange element.
Use the vacuum cleaner equipped with a brush on the tip of the suction nozzle.
Lightly contact the brush on the surface of the heat exchanging element when cleaning. (Do
not crush the heat exchange element while cleaning.)
Caution
•
Do not clean touching strongly with a vacuum cleaner. This may crush the mesh of the heat exchange
elements.
•
Never wash the heat exchange element with water.
•
Have your dealer professionally clean the filter if it is very dirty.
2. Install the air filter securely in place.
3. Put the heat exchange element on the rail and insert it securely in place.
4. Install the maintenance cover securely in place.