Si71-812
Control Functions
Control Functions
47
Nighttime Free Cooling
Operating Condition
Nighttime Free Cooling
Operation <Flow Chart>
Air-conditioner Operation
<STOP>
Yes
Yes
Yes
Yes
Yes
Nighttime Free
Cooling Operation
<ON>
From air-conditioner stop time
Lapsed time
>
Setup time
Indoor temp.
>
Preset temp.+2˚C
Indoor temp.
>
Outdoor temp.
Yes
Yes
No
No
No
No
No
Yes
Yes
Yes
No
No
No
Fan operation & Temperature monitor
<5Min>
Fan operation
<ON (H)or(U-H)tap>
Lapsed time setup
<2hr, 4hr, 6hr, 8hr>
No
Air-conditioner Operation
<RUN>
Temp. monitor operation time
Lapsed time
>
60hr
Indoor temp.
≤
Outdoor temp.
Indoor temp.
≤
Preset temp.
Fan operation Lapsed time
Lapsed time
>
60Min
Standard mode
Fan operation
<STOP>
Standby mode
<60 Min>
( Fan ON time is included )
Summary of Contents for VKM100GAMV1
Page 9: ...Introduction Si71 812 viii ...
Page 43: ...Operation Si71 812 34 Operation ...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Page 103: ...Piping Diagram Si71 812 94 Appendix ...
Page 105: ...Si71 812 ii Index ...