Si71-812
Control Functions
Control Functions
49
1.1.3
Automatic Selection of Ventilation Mode
Unlike the conventional total heat exchanger that only collects the heat on the exhaust air side
to the air supply side, the VKM unit monitors the cooling/heating operation mode and the set
temperature of air conditioners using microcomputer under the interlock control, and detects
indoor and outdoor temperatures under the independent control. In other words, the VKM unit
employs the automatic selection of the ventilation mode that automatically selects the total heat
exchanger ventilation mode or the normal (bypass) ventilation, according to the monitoring
aforementioned.
Operation automatically changes to the optimum pattern to suit conditions.
1.1.4
FRESH-UP Operation
Both the excessive supply mode and the excessive exhaust mode are selectable.
This function creates a more comfortable air environment.
Essential Setting
Changes
Setting changes should be made in the following way.
Mode No. : 18 (group tie up) or 28
Setting switch No.7
Setting position No.1~No.4
Refer to page 85.
Exhaust fan
Air supply fan
DX-coil (cooling)
Damper
Heat exchanger element
(heat recovery)
EA
OA
RA
SA
Humidifying
DX-coil (heating)
Heat exchanger element
(heat recovery)
EA
OA
RA
SA
EA
OA
RA
SA
Cooling
In between (bypass ventilation)
Heating
Automatic
changeover
Automatic
changeover
Supply Fresh-up
(Excessive outdoor air supply)
Exhaust Fresh-up
(Excessive exhaust air supply)
Detail
Supply air volume can be set at a higher level
than the exhaust air by the remote controller.
Exhaust air volume can be set at a higher level
than the supply air by the remote controller.
Major
effects
•
Prevents inflow of toilet odor
•
Prevents inflow of outdoor air in winter
•
Prevents outflow of airborne bacteria
from rooms in a hospital
•
Prevents outflow of odors from rooms in a
nursing home
Application
Offices, etc.
Hospitals, Nursing homes, etc.
Example
Air supply
Normal
ventilation fan
Air exhaust
HRV
(VKM)
Portion of fresh-up
operation
Portion of
exhaust
operation
Air supply
Air exhaust
Sick room
Floor area
HRV
(VKM)
Summary of Contents for VKM100GAMV1
Page 9: ...Introduction Si71 812 viii ...
Page 43: ...Operation Si71 812 34 Operation ...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Page 103: ...Piping Diagram Si71 812 94 Appendix ...
Page 105: ...Si71 812 ii Index ...