Si71-812
Control Functions
Control Functions
51
1.1.6
External Damper Operation (FIELD SUPPLY)
Explanation of
Functions
Intake of outdoor air can be prevented when HRV is switched OFF if this damper is incorporated
in the system.
1. The total heat exchanger’s main unit print board supplies power for external damper.
Essential Wiring
1. Connect one end of the harness to the X15A on the print board and the other end to the
harness leading to the damper via a connector such as a closed connector.
With regard to closed connector, select one that suits wire diameter.
Note: Location of X15A: Refer to next page.
Essential Setting
Changes
The X15A output is at the default setting and is not in operation, so the output setting should be
changed at the LCD of the remote controller.
Setting changes should be made in the following way.
Mode No.: 18 (group tie up) or 28 (per each unit)
Setting switch No.: 3
Setting position No.: 03
In detail, refer to page 85.