Troubleshooting
Si71-812
56
Troubleshooting
2. Troubleshooting
2.1
Error Code Indication
When an abnormality is generated, take necessary measures by referring to displayed error
code.
After the cause of abnormality is removed, operate equipment and check proper functioning.
List of malfunction codes of Remote controller of the HRV-system
In case of the malfunction with the code in white letters on the black background in the unit still
operates.
However, be sure to have it inspected and repaired and as soon as possible.
If other than above error codes are displayed, there is a possibility that the problem in question
has occurred with a combined air conditioner or outdoor unit. See the operation manuals included
with the air conditioners or outdoor units for details.
Operation
lamp
Inspection
indicator
Unit No.
Malfunction
code
Description
Page
On
Off
Blinking
64
Indoor air thermistor malfunction
On
Off
Blinking
65
Outdoor air thermistor malfunction
On
Off
Blinking
6A
Dumper-related malfunction
Blinking
Blinking
Blinking
6A
Dumper-related malfu thermistor malfunction
Blinking
Blinking
Blinking
A1
Printed circuit board fault
On
Off
Blinking
A1
Printed circuit board fault
Blinking
Blinking
Blinking
A9
Electric expansion valve drive error
Blinking
Blinking
Blinking
C4
Liquid piping thermistor (R4T) error (faulty
connection, disconnection short circuit, fault)
Blinking
Blinking
Blinking
C5
Gas piping thermistor (R5T) error (faulty connection,
cut wire, short circuit, fault)
Blinking
Blinking
Blinking
C9
Intake air into coil thermistor (R3T) error (faulty
connection, disconnection, short circuit, fault)
Blinking
Blinking
Blinking
U3
Test run not performed
Blinking
Blinking
Blinking
U5
Transmission error between the unit and remote
controller
Off
Blinking
Off
U5
Setting error of remote controller
Off
Blinking
Off
U8
Transmission error between main remote controller
and sub remote controller
Off
Blinking
Blinking
UA
Incorrect combination with indoor unit and remote
controller.
On
Blinking
On
UC
Central control address over lapping
Blinking
Blinking
Blinking
UE
Transmission error between the unit and centralized
controller
UNIT No.
H
INSPECTION
display
MALFUNCTION CODE
INDOOR UNIT No. in which
a malfunction occurs
OPERATION lamp
Summary of Contents for VKM100GAMV1
Page 9: ...Introduction Si71 812 viii ...
Page 43: ...Operation Si71 812 34 Operation ...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Page 103: ...Piping Diagram Si71 812 94 Appendix ...
Page 105: ...Si71 812 ii Index ...