Si71-812
Troubleshooting
Troubleshooting
63
2.8
“
A9
”
Indoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (20E)
Remote
Controller
Display
A9
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Decision
Conditions
When number of turns can’t be detected even when output voltage to the fan is maximum
Supposed
Causes
Malfunction of moving part of electronic expansion valve
Defect of indoor unit PC board (A2P)
Defect of connecting cable
Troubleshooting
(V2781)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
After connecting, turn the power
supply off and then back on.
Replace the moving part of the
electronic expansion valve.
YES
YES
NO
NO
Replace the connecting cable.
If you turn the power supply off
and turn on again, and it still does
not help, replace the indoor unit
PC board (A2P).
NO
YES
The
electronic
expansion valve is
connected to X7A of the
indoor unit PC
board.
Normal
when coil check
(
∗
1) of the moving part of
the electronic expansion
valve is
checked.
The connecting
cable is short-circuited or
disconnected.
Summary of Contents for VKM100GAMV1
Page 9: ...Introduction Si71 812 viii ...
Page 43: ...Operation Si71 812 34 Operation ...
Page 53: ...Inspection and Maintenance of the Humidifier Si71 812 44 Maintenance ...
Page 91: ...Troubleshooting Si71 812 82 Troubleshooting ...
Page 99: ...Appendix Si71 812 90 Appendix 1 Appendix 1 1 Wiring Diagram VKM50GAMV1 VKM80GAMV1 VKM100GAMV1 ...
Page 100: ...Si71 812 Appendix Appendix 91 VKM50GAV1 VKM80GAV1 VKM100GAV1 ...
Page 103: ...Piping Diagram Si71 812 94 Appendix ...
Page 105: ...Si71 812 ii Index ...