18
|
Commissioning
Installer and user reference guide
104
BS4~12A14AJV1B
VRV 5 branch selector unit
4P695527-1 – 2022.02
a
d
b
c
a
BS unit
b
Air outlet duct
c
Direction airflow
d
Hot wire probe anemometer
18.3.4 To perform a BS unit test run
"17.1.8 Mode 2: field settings"
95] for more information on the settings that
are used.
Respect the sequence indicated in
"18.3.1 About the BS unit test run"
101]. Do
not perform a test run on more than 1 BS unit at a time.
Prerequisite:
All refrigerant piping work is finished.
1
Change field setting [2‑3] to "1". This setting simulates a refrigerant leak and
activates the safety measures according to the field settings that have been
made. See
"18.3.1 About the BS unit test run"
101] to check which units
need a setting change.
2
In case of a configuration with an external alarm, check that the external
alarm warns both audibly (15 dBA above the sound of the surroundings) and
visibly.
3
In case of a configuration with a ventilated enclosure, measure the airflow
rate. See
"18.3.3 About measuring the airflow rate"
103] for more
information.
4
In all configurations, check if no safety measures are activated that are not
intended to activate.
5
Change field setting [2‑3] to "0". This setting deactivates the test run.
6
Change field setting [2‑6] to "1" for all BS units of the system, even those
where the test run was not activated (e.g. downstream BS units in a ventilated
enclosure series configuration). This setting confirms that the safety measures
are working correctly and - in the case of ventilated enclosure – it confirms
that the extraction airflow rate complies to the legal limits.
18.3.5 Troubleshooting during a BS unit test run
Symptom: The damper does not open
Possible causes
Corrective action
Incorrect field settings
Check if all field settings are made
correctly. When in parallel or series
configuration, the field settings of all BS
units in a cluster need to be made
correctly.
Damper wiring is loose
Reattach any loose damper wiring.
Damper blocked
Remove blocking objects.