3
|
Specific installer safety instructions
Installer and user reference guide
10
BS4~12A14AJV1B
VRV 5 branch selector unit
4P695527-1 – 2022.02
3 Specific installer safety instructions
Always observe the following safety instructions and regulations.
Unit installation (see
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
WARNING
In case the safety measures require a ventilated enclosure, respect the following:
▪
Auxiliary devices which may be a potential ignition source shall not be installed in
the duct work (example: hot surfaces with a temperature exceeding 700°C and
electric switching devices).
▪
Only auxiliary devices (example: extraction fan) approved by the manufacturer
are used in the duct work.
WARNING
Do NOT install operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in the duct work.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
WARNING
The fixing method of the unit MUST be in accordance with the instructions from this
manual. See
61].
WARNING
Follow the service space dimensions in this manual for correct installation of the unit.
See
"14.1.1 Installation site requirements of the unit"
CAUTION
Appliance NOT accessible to the general public. Install it in a secured area, protected
from easy access.
This unit is suitable for installation in a commercial and light industrial environment.
CAUTION
This equipment is NOT intended for use in residential locations and will NOT
guarantee to provide adequate protection to radio reception in such locations.
CAUTION
If the metal duct passes through a metal lath, wire lath or metal plate of the wooden
structure, separate the duct and wall electrically.