20
|
Electrical installation
Installer and user reference guide
122
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
b
a
A
b a
c
c
c
d
c
d
c
5~12 HP
14~20 HP
A
A
a
Transmission wiring (possibility 1)
(a)
b
Transmission wiring (possibility 2)
(a)
c
Tie wrap. Fix to factory-mounted low voltage wiring.
(a)
Knockout hole has to be removed. Close the hole to avoid small animals or dirt
from entering.
X1A
b
5~12 HP
14~20 HP
e
a e
c
d
d
d
d
d
d
a b
e
a
Wiring between the units (indoor-outdoor) (F1/F2 left)
b
Internal transmission wiring (Q1/Q2)
c
Plastic bracket
d
Tie wrap (field supply)
e
P-clamp for cable shield earthing
Fix to the indicated plastic brackets using field supplied clamping material.
The wiring for F1/F2 indoor transmission must be shielded wire. The shielding is
earthed via a metal P-clamp (e) (only at outdoor unit). Strip the insulation up to the
shielding mesh, to provide full contact of the earth with the shielding.