20
|
Electrical installation
Installer and user reference guide
124
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
f
Insulation
20.5 To route and fix the power supply
NOTICE
When routing earth wires, secure clearance of 25 mm or more away from
compressor lead wires. Failure to observe this instruction properly may adversely
affect correct operation of other units connected to the same earth.
The power supply wiring can be routed from the front and left side. Fix it to the
lower mounting hole.
c
X1M
a
b
a
c
d
X1M
b
5~12 HP
14~20 HP
A
A
A
d
d
d
d
a
Power supply (possibility 1)
(a)
b
Power supply (possibility 2)
(a)
c
Power supply (possibility 3)
(a)
. Use conduit.
d
Tie wrap
(a)
Knockout hole has to be removed. Close the hole to avoid small animals or dirt
from entering.
20.6 To connect the power supply
NOTICE
Never connect the power supply to transmission wiring terminal block. Otherwise
the entire system may break down.