25
|
Troubleshooting
Installer and user reference guide
165
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
Main
code
Sub code
Cause
Solution
SVEO
(a)
SVS
(b)
Master Slave 1
High pressure sensor malfunction
(S1NPH): open circuit - main PCB
(X32A)
Check connection on PCB or
actuator.
High pressure sensor malfunction
(S1NPH): short circuit - main PCB
(X32A)
Check connection on PCB or
actuator.
Low pressure sensor malfunction
(S1NPL): open circuit - main PCB
(X31A)
Check connection on PCB or
actuator.
Low pressure sensor malfunction
(S1NPL): short circuit - main PCB
(X31A)
Check connection on PCB or
actuator.
Transmission outdoor unit -
inverter: INV1 transmission
trouble - main PCB (X20A, X28A,
X40A)
Check connection.
Transmission outdoor unit -
inverter: FAN1 transmission
trouble - main PCB (X20A, X28A,
X40A)
Check connection.
Transmission outdoor unit -
inverter: FAN2 transmission
trouble - main PCB (X20A, X28A,
X40A)
Check connection.
Transmission main PCB – sub PCB
– main PCB (X20A), sub PCB (X2A,
X3A)
Check connection.
INV1 unbalanced power supply
voltage
Check if power supply is within
range.
Reversed power supply phase
malfunction
Correct phase order.
Reversed power supply phase
malfunction
Correct phase order.
INV1 voltage power shortage
Check if power supply is within
range.
INV1 power phase loss
Check if power supply is within
range.