25
|
Troubleshooting
Installer and user reference guide
166
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
Main
code
Sub code
Cause
Solution
SVEO
(a)
SVS
(b)
Master Slave 1
Malfunction code: system test run
not yet executed (system
operation not possible)
Execute system test run.
An error occurred during the test
run
Re-execute the test run.
,
Test run aborted
Re-execute the test run.
,
Test run aborted due to
communication issues
Check the communication wires
and re-execute the test run.
Commissioning of BS unit safety
system is not completed
Complete commisioning of BS unit
safety system. Refer to BS unit
manual for more information.
Indoor unit communication error
Check user interface connection.
,
Malfunction code: faulty wiring to
Q1/Q2
Check Q1/Q2wiring.
Too many indoor units are
connected to F1/F2 line
Check indoor unit amount and
total capacity connected.
Warning because there is an error
on another unit (indoor/BS unit)
Check if other indoor units/BS
units have malfunction and
confirm indoor unit mix is allowed.
Connection malfunction over
indoor units or type mismatch
Check if other indoor units have
malfunction and confirm indoor
unit mix is allowed.
Connection malfunction over
indoor units or type mismatch
Check if other indoor units have
malfunction and confirm indoor
unit mix is allowed.
Wrong unit combination (multi
system)
Check if unit types are compatible.
Wrong outdoor unit connected
Disconnect the outdoor unit.
No BS unit connected
Connect a BS unit.
Old BS unit connected
Disconnect the BS unit.
BS unit refrigerant type
abnormality
Check BS unit refrigerant type
BS unit DIP switch abnormality
Check the DIP switches of the BS
unit.
Mismatch between wiring path
and piping path during test run
Mistake detected during BS unit
and indoor unit connection check
(see
Confirm wiring between indoors
and BS units.
Refer to BS unit manual for
correct way of wiring.