18
|
Piping installation
Installer and user reference guide
84
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
Indoor unit capacity index
Refrigerant branch kit
290≤x<640
KHRQ23M64H
≥640
KHRQ23M75H
▪
For refnet joints between BS unit and indoor units
Indoor unit capacity index
Refrigerant branch kit
≤250
KHRQ22M20TA
INFORMATION
Maximum 8 branches can be connected to a header.
▪
Use the branch kit BHFQ23P907A for an outdoor multi connection piping kit for 2
outdoor units.
18.1.6 Installation limitations
The illustration and table below show the installation limitations.
g
a
f
e
b
c
g
g
d
g
g
g
gg
g
a, b
See table below
c
Maximum limit of 16 downstream ports of BS units in refrigerant flow-through.
Unused ports must also be counted. E.g. 16 ports=BS12A+BS4A or BS8A+BS4A
+BS4A
d
At least one indoor unit must be connected to a BS unit
e
Combine two ports when indoor unit capacity is over 140
f
Cooling only indoor units cannot be installed. All indoor units must be connected to
the branch pipes of a BS unit
g
BS unit