20
|
Electrical installation
Installer and user reference guide
120
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
Single outdoor unit
Model
Z
max
[Ω]
Minimum S
sc
value [kVA]
REYA18
—
6062
REYA20
—
7274
Multiple outdoor units
Model
Z
max
[Ω]
Minimum S
sc
value [kVA]
REYA10
—
5196
REYA13
—
5387
REYA16
—
5577
REYA18
—
6599
REYA20
—
6945
REYA22
—
7967
REYA24
—
8158
REYA26
—
8833
REYA28
—
9526
INFORMATION
Multi units are standard combinations.
20.1.5 Safety device requirements
The power supply must be protected with the required safety devices, i.e. a main
switch, a slow blow fuse on each phase and an earth leakage protector in
accordance with the applicable legislation.
For standard combinations
Selection and sizing of the wiring should be done in accordance with the applicable
legislation based on the information mentioned in the table below.
INFORMATION
Multi units are standard combinations.
Single outdoor unit
Model
Minimum circuit ampacity
Recommended fuses
REMA5
15.0 A
20 A
REYA8
16.1 A
20 A
REYA10
22.0 A
25 A
REYA12
24.0 A
32 A
REYA14
27.0 A
32 A
REYA16
31.0 A
40 A
REYA18
35.0 A
40 A
REYA20
42.0 A
50 A