21
|
Configuration
Installer and user reference guide
135
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
Result
Description
No data
Leak detection failure due to abnormal operation
No leak detected
Leak detected
For instructions on how to use the leak detection function, see
147].
[1‑34]
Shows the remaining days until the next automatic leak detection (if automatic leak
detection function is activated).
When the automatic leak detection function was activated through mode 2
settings, it is possible to see within how many days, the automatic leak detection
will be performed. Depending on the chosen field setting, the automatic leak
detection function can be programmed one time into the future or on perpetual
basis.
Indication is given in remaining days and is between 0 and 365 days.
[1‑40] [1‑41]
Code
Shows ...
[1‑40]
The current cooling comfort setting
[1‑41]
The current heating comfort setting
See
"21.2 Energy saving and optimum operation"
142] for more details about
this setting.
21.1.8 Mode 2: field settings
[2‑8]
T
e
target temperature during cooling operation.
[2‑8]
T
e
target [°C]
0 (default)
Auto
2
6
3
7
4
8
5
9
6
10
7
11
For more information and advice about the impact of these settings, see
"21.2 Energy saving and optimum operation"
[2‑9]
T
c
target temperature during heating operation.
[2‑9]
T
c
target [°C]
0 (default)
Auto