19
|
Charging refrigerant
Installer and user reference guide
123
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
19.6 Error codes when charging refrigerant
If a malfunction occurs, close valve A immediately. Confirm the malfunction code
and take corresponding action,
"25.3 Solving problems based on error
176].
19.7 Checks after charging refrigerant
▪
Are all stop valves open?
▪
Is the amount of refrigerant, that has been added, recorded on the refrigerant
charge label?
NOTICE
Make sure to open all stop valves after (pre-) charging the refrigerant.
Operating with the stop valves closed will damage the compressor.
19.8 To fix the fluorinated greenhouse gases label
1
Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a
If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of
a
.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e Quantity of fluorinated greenhouse gases
of the total refrigerant charge
expressed as tonnes CO
2
equivalent.
f
GWP = Global Warming Potential
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label.
2
Fix the label on the inside of the outdoor unit near the gas and liquid stop
valves.