21
|
Configuration
Installer and user reference guide
154
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
[2‑49]
Height difference setting.
[2‑49]
Description
0 (default)
—
1
In case the outdoor unit is installed in the highest
position (indoor units are installed on a lower position
than outdoor units) and the height difference between
the lowest indoor unit and the outdoor unit exceeds
50 m, the setting [2‑49] has to be changed to 1.
Other changes/limitations to the circuit apply. For more information see
"18.1.8 Single and multi-outdoor-unit combinations"
98].
[2‑54]
Indoor unit connection setting.
[2‑54]
Description
0 (default)
Direct connection to the outdoor unit is not possible
1
Direct connection to the outdoor unit is allowed
[2‑60]
Supervisor remote controller setting. A power reset is required to save this setting.
For details about the supervisor remote controller, see
65] or refer to the remote controller installation and user
reference guide.
[2‑60]
Description
0 (default)
No supervisor remote controller connected to the
system
1
Supervisor remote controller connected to system
[2‑65]
Automatic leak detection interval time.
This setting is used in conjunction with setting [2‑88].
[2‑65]
Time between automatic leak detection executions
[days]
0 (default)
365
1
180
2
90
3
60
4
30
5
7
6
1
[2‑81]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].