18
|
Piping installation
Installer and user reference guide
98
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
18.1.8 Single and multi-outdoor-unit combinations
Connection with only VRV DX indoor units
H3
H1
E
A
B2
G
F
B1
a
b
c
c
d
c
d
d
e
b
D
H2
C2
C4
C3
C1
a
Outdoor unit
b
VRV DX indoor unit
c
Safety valve unit (SV)
d
VRV DX indoor unit (duct)
e
VRV DX indoor unit (large duct)
Pipe
Maximum length (actual/equivalent)
Longest pipe from the outdoor unit or
the last multi-outdoor piping branch (A
+B1+C1, A+B2+C2, A+B1+C3, A+B1+D
+C4, A+F+G)
165 m/190 m
(a)
135 m/160 m
(a)(b)
Longest pipe after the first branch or SV
unit (B1+C1, B2+C2, B1+C3, B1+D+C4, F
+G)
40 m/—
(c)
In case of a multi-outdoor setup:
longest pipe from the outdoor unit to
the last multi-outdoor piping branch (E)
10 m/13 m
Total pipe length
1000 m/—
500 m/—
(b)
(a)
If the equivalent piping length is more than 90 m, size up the main piping according to
"18.1.4 To select the piping size"
(b)
In case of multi-outdoor-unit combinations.