2 Specific installer safety instructions
Installation and operation manual
6
SV1ASV4~8A14AJV1B
VRV 5 safety valve unit
4P709466-1 – 2023.09
CAUTION
Do NOT insert fingers, rods or other objects into the air
inlet (damper).
WARNING
Safety shut-off valves shall only be replaced with valves
specified by the appliance manufacturer.
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover
is removed.
DANGER: RISK OF BURNING/SCALDING
WARNING
Prevent hazards due to inadvertent resetting of the thermal
cut-out: power to this appliance MUST NOT be supplied
through an external switching device, such as a timer, or
connected to a circuit that is regularly turned ON and OFF
by the utility.
WARNING
▪ When carrying out an inspection on the switch box of
the unit, ALWAYS make sure that the unit is
disconnected from the mains. Turn off the respective
circuit breaker.
▪ When a safety device was activated, stop the unit and
find out why the safety device was activated before
resetting it. NEVER shunt safety devices or change
their values to a value other than the factory default
setting. If you are unable to find the cause of the
problem, call your dealer.
2.1
Instructions for equipment using
R32 refrigerant
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.
WARNING
The appliance shall be stored as follows:
▪ in such a way as to prevent mechanical damage.
▪ in a well-ventilated room without continuously operating
ignition sources (example: open flames, an operating
gas appliance or an operating electric heater).
▪ in a room with dimensions as specified in
WARNING
Make sure installation, servicing, maintenance and repair
comply with instructions from Daikin and with applicable
legislation (for example national gas regulation) and are
executed ONLY by authorised persons.
WARNING
Refrigerant sensors of the refrigerant detection system
shall only be replaced with refrigerant sensors specified by
the appliance manufacturer.
WARNING
Safety shut-off valves shall not be reset until the room has
been ventilated. Resetting may result in additional
flammable refrigerant to be released into the room.
WARNING
▪ Take precautions to avoid excessive vibration or
pulsation to refrigeration piping.
▪ Protect the protection devices, piping and fittings as
much as possible against adverse environmental
effects.
▪ Provide space for expansion and contraction of long
runs of piping.
▪ Design and install piping in refrigerating systems such
as to minimise the likelihood of hydraulic shock
damaging the system.
▪ Mount the indoor equipment and pipes securely and
protect them to avoid accidental rupture of equipment
or pipes in case of events such as moving furniture or
reconstruction activities.
CAUTION
Do NOT use potential sources of ignition in searching for
or detection of refrigerant leaks.
NOTICE
▪ Do NOT re-use joints and copper gaskets which have
been used already.
▪ Joints made in the installation between parts of the
refrigerant system shall be accessible for maintenance
purposes.
See
"12.3 To determine the required safety measures"
14] to
check if your system meets the R32 safety requirements.
Summary of Contents for VRV 5
Page 47: ......