Troubleshooting by Error Code
SiUS342303E
251
Part 6 Service Diagnosis
3.5 Indoor Unit Control PCB Abnormality
Applicable
Models
All indoor unit models
Error Code
A1
Method of Error
Detection
Check data from EEPROM.
Error Decision
Conditions
When data could not be correctly received from the EEPROM
EEPROM : Type of nonvolatile memory. Maintains memory contents even when the power supply
is turned OFF.
Supposed
Causes
Defective indoor unit control PCB
External factor (Noise, etc.)
Troubleshooting
T
u
rn the power s
u
pply OFF,
then the power ON again.
Does the
system ret
u
rn to
normal?
YES
Caution
Be s
u
re to t
u
rn off the power switch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Replace the indoor
u
nit
control PCB (A1P).
The indoor
u
nit control PCB
(A1P) is normal.
External factor other than
error (for example, noise
etc.).
NO