Troubleshooting by Error Code
SiUS342303E
323
Part 6 Service Diagnosis
Reference
Troubleshooting
CHECK 4
Refer to page 376.
CHECK 4
Is the power
transistor of the fan
driver normal?
CHECK 4
Is the power
transistor normal?
Is the
insulation to
ground resistance of the
relevant compressor 100
k
or more?
The error could have resulted from
external factors other than failures
(e.g. external noise or thunder).
YES
Replace the compressor and the
inverter PCB together.
Replace the inverter PCB.
NO
NO
YES
Replace the inverter PCB and the fan
PCB.
Replace the inverter PCB.
NO
YES
Turn OFF the power supply
once, and then turn it ON
again.
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Return to normal?