SiUS342303E
Troubleshooting by Error Code
Part 6 Service Diagnosis
354
YES
NO
4 or more outdoor
units are connected using
the outdoor unit multi
transmission
wirings.
YES
YES
There is
an error in the
connection of
indoor-outdoor, indoor-indoor, and
outdoor multi transmission
wirings.
Modify the outdoor unit multi
transmission wirings, and then
reset the power supply.
Replace the outdoor unit main
PCB (A1P).
Replace the outdoor unit main
PCB (A1P).
Rectify the error in the connection
of transmission wirings, and then
reset the power supply.
NO
The capacity to
connect indoor units
falls within the specified
range.
Check the capacity to connect
indoor units.
Diagnosis Flowchart-6
(Connection 4 or more outdoor units
to the same system)
Error code
Sub code
U7-07
Diagnosis Flowchart-7
(Connection of excess indoor units
for test operation)
Error code
Sub code
U7-11
NO