1.4 Outdoor-Air Processing Unit
FXMQ48/72/96MFVJU*
1. SH control: Superheating control of heat exchanger outlet
2. SC control: Subcooling control of heat exchanger outlet
No. in piping
diagram
Electric symbol
Name
Function
(1)
Y1E
Electronic expansion valve
Used to control the flow rate of refrigerant, and make the SH
control (
1) while in cooling.
(2)
Y1S
Solenoid valve
Used to bypass hot gas while in heating with thermostat OFF.
Closed while in cooling.
(3)
—
Capillary tube
Used to reduce pressure from high to low in bypassing hot gas.
(4)
R1T
Suction air thermistor
Used to turn ON or OFF the thermostat.
(5)
R2T
Liquid pipe thermistor
Used to control the opening degree of electronic expansion valve
under the SC control (
2).
(6)
R3T
Gas pipe thermistor
Used to control the opening degree of electronic expansion valve
under the SH control.
(7)
R4T
Discharge air thermistor
Used to control the electronic expansion valve opening and
thermostat ON/OFF so as to keep the discharge air temperature
at the set temperature.
C: 4D01
8
650D
Heat exchanger
Distributor
Fan
Filter
Filter
Filter
Electronic
expansion valve
Capillary
tube
Solenoid
valve
Check
valve
Gas pipe
connection port
Liquid pipe
connection port
(5)
(7)
(6)
(3)
(2)
(1)
(4)
Summary of Contents for VRV EMERION RXYQ-AATJA
Page 1: ...Service Manual Heat Pump 60 Hz RXYQ AATJA 208 230 V RXYQ AAYDA 460 V SiUS342303E...
Page 410: ...Wiring Diagrams SiUS342303E 403 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 411: ...SiUS342303E Wiring Diagrams Part 7 Appendix 404 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 416: ...Wiring Diagrams SiUS342303E 409 Part 7 Appendix FXHQ12 24 36MVJU 3D048116C...
Page 417: ...SiUS342303E Wiring Diagrams Part 7 Appendix 410 FXAQ07 09 12 18 24PVJU 3D075354F...
Page 424: ...Wiring Diagrams SiUS342303E 417 Part 7 Appendix VAM1200GVJU 3D073270D...