Specifications
Si39-504
28
Specifications
Slim Ceiling Mounted Duct Type (without Drain Pump)
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length; 7.5m, level difference :
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Model
FXDQ20NVET
FXDQ25NVET
FXDQ32NVET
1 Cooling Capacity (19.5°CWB)
kcal/h
2,000
2,500
3,200
Btu/h
7,800
9,900
12,600
kW
2.3
2.9
3.7
2 Cooling Capacity (19.0°CWB)
kW
2.2
2.8
3.6
3 Heating Capacity
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
Casing
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H×W×D)
mm
200×900×620
200×900×620
200×900×620
Coil (Cross
Fin Coil)
Rows×Stages×Fin Pitch
mm
2×12×1.5
2×12×1.5
2×12×1.5
Face Area
m²
0.176
0.176
0.176
Fan
Model
—
—
—
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output × Number
of Units
W
62×1
62×1
62×1
Air Flow Rate (H/L)
m³/min
9.5/7.5
9.5/7.5
10.5/8.5
External Static Pressure
Pa
44-15 5
44-15 5
44-15 5
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polyethylene
Foamed Polyethylene
Foamed Polyethylene
Air Filter
Removal / Washable / Mildew Proof
Removal / Washable / Mildew Proof
Removal / Washable / Mildew Proof
Piping
Connections
Liquid Pipes
mm
φ
6.4 (Flare Connection)
φ
6.4 (Flare Connection)
φ
6.4 (Flare Connection)
Gas Pipes
mm
φ
12.7 (Flare Connection)
φ
12.7 (Flare Connection)
φ
12.7 (Flare Connection)
Drain Pipe
mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
Machine Weight (Mass)
kg
26
26
26
6 Sound Level (H/L)
dBA
33/29
33/29
33/29
Safety Devices
Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Standard Accessories
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Operation Manual,
Installation Manual,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Drawing No.
C : 3D049693
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
Summary of Contents for VRV II RXYQ5MATL
Page 53: ...Specifications Si39 504 42 Specifications...
Page 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Page 161: ...Field Setting Si39 504 150 Test Operation...
Page 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Page 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Page 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Page 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Page 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Page 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Page 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Page 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Page 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Page 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Page 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Page 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Page 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Page 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Page 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...