Si39-502A
Protection Control
Function
69
4.
Protection Control
4.1
High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
[In cooling operation]
In the case of multi-outdoor-unit system, each outdoor unit performs this control
individually in the following sequence.
[In heating operation]
In the case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
High pressure not limited
Pc>3.47MPa
High pressure standby
INV upper limit frequency = 210 Hz
High pressure limited
Pc>3.47MPa
Pc>3.64MPa
Pc<3.24MPa
Pc>3.55MPa
STD compressor
standby for 5 mins
Pc: HP pressure sensor detection
value for each outdoor unit
When occurring 3 times within
30 min., HPS is activated without high
pressure standby, thus outputting the
malfunction code “E3”.
INV upper limit frequency :
3-step / 10 sec down from
current compressor frequency
INV upper limit frequency:
1-step / 15 sec up from
current compressor frequency
High pressure not limited
Pc>3.32MPa
System load down 7 steps
High pressure limited
Pc>3.32MPa
Master unit: 52 Hz + OFF + OFF
Slave unit: All units stop.
Pc>3.42MPa
High pressure standby
Pc>3.64MPa
Pc<2.9MPa
Pc: HP pressure sensor detection
value for master unit
When occurring 3 times within
30 min., HPS is activated without high
pressure standby, thus outputting the
malfunction code “E3” .
Summary of Contents for VRV II RXYQ8MY1K
Page 53: ...Specifications Si39 502A 42 Specifications...
Page 143: ...Field Setting Si39 502A 132 Test Operation...
Page 258: ...Si39 502A Wiring Diagrams for Reference Appendix 247 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 260: ...Si39 502A Wiring Diagrams for Reference Appendix 249 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 264: ...Si39 502A Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 265: ...Wiring Diagrams for Reference Si39 502A 254 Appendix FXMQ200M 250MVE 3D039621A...
Page 266: ...Si39 502A Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C...
Page 267: ...Wiring Diagrams for Reference Si39 502A 256 Appendix FXAQ20M 25M 32M 40M 50M 63MVE 3D034206A...
Page 269: ...Wiring Diagrams for Reference Si39 502A 258 Appendix FXUQ71M 100M 125MV1 3D044973...
Page 270: ...Si39 502A Wiring Diagrams for Reference Appendix 259 FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Page 271: ...Wiring Diagrams for Reference Si39 502A 260 Appendix FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Page 272: ...Si39 502A Wiring Diagrams for Reference Appendix 261 BEVQ50MVE 3D046579A Notes...
Page 273: ...Wiring Diagrams for Reference Si39 502A 262 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Page 285: ...Piping Installation Point Si39 502A 274 Appendix...
Page 293: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 502A 282 Appendix...
Page 307: ...Si39 502A iv Index...