Outline of Control (Indoor Unit)
Function
83
6.4
Thermostat Control While in Normal Operation
VRV multi systems are set at factory to thermostat control mode using the remote controller.
While in normal thermostat differential control mode (i.e., factory set mode), the thermostat
turns OFF when the system reaches a temperature of -1°C from the set temperature while in
cooling operation or of +1°C from that while in heating operation.
While in a single remote controller group control, the body thermostat is only used fro this
control.
Furthermore, while in heating operation, cassette-mounted indoor units conduct the thermostat
control by a value compensated by -2°C for the value detected with the body thermostat.
(Through field settings, the thermostat differential setting can be changed from 1°C to 0.5°C.
For details on the changing procedure, refer to information on page onward.)
6.5
Thermostat Control in Dry Operation
While in dry operation, the thermostat control is conducted according to a suction temperature
at the time of starting the dry operation.
Assuming that the suction air temperature at the time of starting the dry operation is Tro and the
suction air temperature in operation is Tr,
Furthermore, while in dry operation mode, fans operate at L flow rate, stops for a period of six
minutes while the thermostat is OFF, and then return to operation at L flow rate. (This control is
used to prevent a rise in indoor temperature while in thermostat OFF mode.)
Cooling operation:
Heating operation:
Normal
operation
Thermostat OFF
Tr < Set temperature -1
ºC
Normal
operation
Thermostat OFF
Tr > Set tempe1
º
C
Tr: Temperature detected with the suction
air thermistor (R1T)
when Tro
≤
24.5
º
C:
when Tro > 24.5
º
C:
In dry operation
In dry operation
Tr < Tro - 1
º
C
Tr < Tro - 1.5
º
C
Thermostat OFF
Thermostat OFF
Tro: Suction air temperature at the
time of starting the dry operation
Tr: Temperature detected with the
suction air thermistor (R1T)
Summary of Contents for VRV II RXYQ8MY1K
Page 53: ...Specifications Si39 502A 42 Specifications...
Page 143: ...Field Setting Si39 502A 132 Test Operation...
Page 258: ...Si39 502A Wiring Diagrams for Reference Appendix 247 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 260: ...Si39 502A Wiring Diagrams for Reference Appendix 249 FXKQ25M 32M 40M 63MVE 3D039564A...
Page 264: ...Si39 502A Wiring Diagrams for Reference Appendix 253 FXMQ40M 50M 63M 80M 100M 125MVE 3D039620A...
Page 265: ...Wiring Diagrams for Reference Si39 502A 254 Appendix FXMQ200M 250MVE 3D039621A...
Page 266: ...Si39 502A Wiring Diagrams for Reference Appendix 255 FXHQ32M 63M 100MVE 3D039801C...
Page 267: ...Wiring Diagrams for Reference Si39 502A 256 Appendix FXAQ20M 25M 32M 40M 50M 63MVE 3D034206A...
Page 269: ...Wiring Diagrams for Reference Si39 502A 258 Appendix FXUQ71M 100M 125MV1 3D044973...
Page 270: ...Si39 502A Wiring Diagrams for Reference Appendix 259 FXAQ20MH 25MH 32MH 40MH 50MHV1 3D046348A...
Page 271: ...Wiring Diagrams for Reference Si39 502A 260 Appendix FXLQ20MH 25MH 32MH 40MH 50MHV1 3D046787A...
Page 272: ...Si39 502A Wiring Diagrams for Reference Appendix 261 BEVQ50MVE 3D046579A Notes...
Page 273: ...Wiring Diagrams for Reference Si39 502A 262 Appendix BEVQ71M 100M 125MVE 3D044901A Notes...
Page 285: ...Piping Installation Point Si39 502A 274 Appendix...
Page 293: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 502A 282 Appendix...
Page 307: ...Si39 502A iv Index...