Field Setting
Si37-701
192
Test Operation
No.
Setting item
Description
38
Emergency
operation
(Setting for the unit
1 operation
prohibition in multi-
outdoor-unit
system)
Used to temporarily prohibit the applicable outdoor unit
from operating should there be any faulty part in multi-
outdoor-unit system. Since the comfortable environment
is extremely impaired, prompt replacement of the part is
required.
39
Emergency
operation
(Setting for the unit
2 operation
prohibition in multi-
outdoor-unit
system)
40
Emergency
operation
(Setting for the unit
3 operation
prohibition in multi-
outdoor-unit
system)
41
Prevention of
minute heating
operation by
heating thermostat
OFF unit or non-
heating-operation
unit
Make this setting to shorten the BS Cool-Heat selection
control time.
However, make the setting, pay careful attention to the
following:
• If the refrigerant piping between each BS unit
connected to outdoor unit and indoor unit is not more
than 10 m in length, this setting will be enabled.
• If the refrigerant piping between BS unit and indoor unit
is long in length, refrigerant passing sounds may
become louder at the time of BS Cool-Heat selection.
• This setting shortens the Cool-Heat selection time of all
BS units provided in the same refrigerant system.
42
Setting of BS Cool-
Heat selection
control time
Make this setting to prevent a rise in room temperature
due to minute heating capacity generated by heating
thermostat OFF unit or non-heating-operation unit while
in heating operation.
• Used to prevent minute heating operation by setting
the BS unit to COOL while in heating thermostat OFF
or non-heating-operation mode.
• With the BS unit set to default, enabling the minute
heating prevention setting of outdoor unit will enable
the minute heating prevention setting of all BS units
connected to the outdoor unit. (BS unit default setting)
• To make this setting by BS unit, make a change to the
minute heating prevention setting of the BS unit. (In
this case, enable the outdoor unit setting.)
51
Set-up of master
and slave units for
multi outdoor units
Set up master and slave units for multi-connection
outdoor units.
After setting up, press the
button for
5 seconds or more.
The numbers in the "No." column represent the number of times to press
the SET (BS2) button.
BS5 (REWIRING)
Summary of Contents for VRV III REYQ10PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701 ...
Page 59: ...Specifications Si37 701 48 Specifications ...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit ...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219 ...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH ...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743 ...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742 ...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741 ...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A ...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C ...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E ...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E ...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E ...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A ...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359 ...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C ...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1 ...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B ...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D ...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C ...
Page 423: ...Piping Installation Point Si37 701 412 Appendix ...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix ...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix ...
Page 447: ...Si37 701 iv Index ...