Si37-701
Special Control
Function
123
3.7
Stopping Operation
3.7.1 When System is in Stop Mode (Normal operation stop)
This mode is used to define actuator operations when the system stops.
3.7.2 Stop due to Malfunction
In order to protect compressors, if any of the following items has an abnormal value, the system will make "stop with
thermostat OFF" and the malfunction will be determined according to the number of retry times.
Actuator
Symbol
Elect.
symbol
Operation
REYQ
REMQ
REYQ8~16P
REMQ8P
REMQ10•12P
REMQ14•16P
Compressor1
—
M1C
M1C
OFF
OFF
OFF
OFF
Compressor2
—
M2C
M2C
OFF
—
OFF
OFF
Compressor3
—
M3C
M3C
—
—
—
OFF
Outdoor unit fan1
—
M1F
M1F
OFF
OFF
OFF
OFF
Outdoor unit fan2
—
M2F
M2F
OFF
—
—
OFF
Electronic expansion valve
(Main)
EVM
Y1E
Y3E
Y1E
0 pls
Electronic expansion valve
(Supercooling)
EVT
Y2E
Y5E
Y3E
0 pls
Electronic expansion valve
(Refrigerant charge)
EVJ
Y4E
Y2E
80 pls
Four way valve (Heat
exchanger switch)
20SA
Y2S
Y9S
Y3S
Holds
Four way valve (High/low
pressure gas pipe switch)
20SB
Y8S
Y2S
Holds
Solenoid valve (Main bypass)
SVE
Y5S
Y10S
Y6S
OFF
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
Solenoid valve (Refrigerant
regulator liquid pipe )
SVL
Y3S
Y4S
OFF
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG
Y1S
Y1S
OFF
Solenoid valve (Refrigerant
regulator exhaust pipe)
SVO
Y7S
Y7S
OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT
Y6S
Y8S
OFF
Ending conditions
—
Indoor unit thermostat is turned ON.
Item
Judgment Criteria
Malfunction Code
1. Abnormal low pressure level
0.07MPa
E4
2. Abnormal high pressure level
4.0MPa
E3
3. Abnormal discharge pipe temperature level
135
°
C
F3
4. Abnormal power supply voltage
Reverse-phase power supply
U1
5. Abnormal inverter current level
16.1A: 260 sec.
L8
6. Abnormal radiator fin temperature level
93
°
C
L4
Summary of Contents for VRV III REYQ10PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701 ...
Page 59: ...Specifications Si37 701 48 Specifications ...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit ...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219 ...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH ...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743 ...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742 ...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741 ...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A ...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C ...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E ...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E ...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E ...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A ...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359 ...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C ...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1 ...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B ...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D ...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C ...
Page 423: ...Piping Installation Point Si37 701 412 Appendix ...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix ...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix ...
Page 447: ...Si37 701 iv Index ...