6
English
ADJUSTMENT (Refer to figure 4)
For adjustment the desired temperature, fan
speed and air flow direction (only for the
remote controller BRC1A51: FXC, FXF, FXH,
FXK, FXA), follow the procedure shown below.
Press the temperature setting button and set
the desired temperature.
Each time this button is pressed, the tem-
perature setting rises or lowers 1°C.
NOTE
• Set the temperature within the operation range.
• The temperature setting is impossible for fan
only operation.
Press the fan speed control button and select
the fan speed of your preference.
NOTE
• For machine protection the system may con-
trol the air flow rate automatically.
• The air flow rate may be adjusted automati-
cally depending on the room temperature or
the fan may stop immediately. This is not a
malfunction.
• It may take sometime for finishing to change
the air flow rate.
This is normal operation.
Press air flow direction adjust button.
Refer to the chapter “6-3 ADJUSTING THE
AIR FLOW DIRECTION” for details.
STOPPING THE SYSTEM (Refer to figure 4)
Press the on/off button once again.
The operation lamp goes off and the system
stops operation.
NOTE
• The fan may keep on running for about
1 minute after the heating operation stops
for removing the heat in the indoor unit.
• Do not turn off the power immediately after
the unit stops.
The system need at least 5 minutes for
residual operation of drain pump device.
Turning off the power immediately will cause
water leak or trouble.
EXPLANATION OF HEATING OPERATION
• In general, heating operation may take longer to
reach the set temperature than in cooling operation.
We recommend starting the operation which was
used before using timer operation.
• The following operation is performed in order to
prevent the heating capacity from dropping or
cold air from blowing.
Defrost operation
• In heating operation, freezing of the outdoor
unit heat exchanger increases. Heating
capability decreases and the system goes
into defrost operation.
• The airflow will be set to breeze or stop.
• If stopped, the display of the remote control-
ler shows “
”.
• Once the airflow is set to breeze or stop, the
air conditioner will return to the previous
state in approximately 10 to 15 minutes.
Hot start
• In order to prevent cold air from blowing out
of an indoor unit at the start of heating oper-
ation, the indoor fan is automatically
stopped. The display of the remote controller
shows “
”.
• The heating capacity drops as the outside tem-
perature falls. If this happens, use another heat-
ing device together with the unit. (When using the
appliances which produce open fire together, ven-
tilate a room constantly.)
Do not place appliances which produce open fire
in places exposed to the air flow from the unit or
under the unit.
• It takes some time for the room to warm up from
the time the unit is started since the unit is a hot-air
circulatory system to warm the entire room.
• If the hot air rises to the ceiling, leaving the area
above the floor cold, we recommend using the cir-
culator (the indoor fan for circulating air). Contact
your dealer for details.
6-2 PROGRAM DRY OPERATION
• The program dry function deprives the room
of moisture while the air conditioner is in inter-
mittent weak cooling operation so that the
room temperature will not become too low.
• The microcomputer automatically controls
the temperature and fan speed, so these
cannot be set using the remote controller.
• This function is not available if the room tem-
perature is 20°C or lower.
• This function does not controls the humidity.
• FXL and FXN type indoor unit can not oper-
ate program dry operation.
FOR SYSTEMS WITHOUT COOL/HEAT SELEC-
TOR (Refer to figure 5)
NOTE
• If “
” (Cooling operation) is not displayed, refer
to “6-1 COOLING, HEATING, AUTOMATIC AND
FAN ONLY OPERATION”, and set “
” (Cooling
operation).
Unless the air conditioner is set to “
” (Cooling
operation), the air conditioner cannot be switched
over to “
” (program dry operation).
3
4
5
6
01_EN_3P201178-2B.fm Page 6 Wednesday, April 25, 2007 3:51 PM
Summary of Contents for VRV III REYQ10PY1B
Page 3: ...2 1 4 3 5 6 7 1 7 3 7 2 ...
Page 19: ...3P201178 2B EM07A012 0705 HT ...