Outline of Control (Indoor Unit)
SiBE37-701
144
Function
6.2.4 Thermostat Control with Operation Mode Set to "AUTO"
When the operation mode is set to "AUTO" on the remote controller, the system will conduct the
temperature control shown below.
Furthermore, setting changes of the differential value (D°C) can be made according to
information in the "Field settings with remote controller (p. 160 and later)" section.
: Factory setting
Mode
No.
Setting
switch No.
Contents of setting
Setting position No.
01
02
03
04
05
06
07
08
12
4
Differential value while in "AUTO"
operation mode
0°C
1°C
2°C
3°C
4°C
5°C
6°C
7°C
Set heating temperature
(A-D)
°
C
Set cooling temperature
A
°
C
Display change
Cooling
→
Heating
Display change
Heating
→
Cooling
Cooling thermostat ON
Cooling thermostat OFF
Heating thermostat ON
Heating thermostat OFF
2
D
Differential value :0
°
C
27
°
C
25
°
C
30
°
C
Set cooling/
heating temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 1
°
C
26
°
C
24.5
°
C
29
°
C
Set heating temp.
27
°
C
Set cooling temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 2
°
C
24
°
C
28
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 3
°
C
23.5
°
C
Heating mode
Cooling mode
Control temp.
25
°
C
Set heating temp.
27
°
C
Set cooling temp.
24
°
C
Set heating temp.
27
°
C
Set cooling temp.
Differential value set to 4
°
C
26
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 5
°
C
22
°
C
22.5
°
C 25
°
C
Set heating temp.
27
°
C
Set cooling temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 6
°
C
22
°
C
24
°
C
Heating mode
Cooling mode
Control temp.
Differential value set to 7
°
C
21.5
°
C 23
°
C
Heating mode
Cooling mode
Control temp.
21
°
C
Set heating temp.
27
°
C
Set cooling temp.
20
°
C
Set heating temp.
27
°
C
Set cooling temp.
23
°
C
Set heating temp.
27
°
C
Set cooling temp.
(Ex.) When automatic cooling temperature is set to 27
°
C:
D
°
C
3
°
C
(
+2)
°
C
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...