Field Setting
SiBE37-701
194
Test Operation
3.1.6 Detailed Explanation of Setting Modes
(1)
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Set Time
(2) Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
Setting Table
(3) Selection of Thermistor
Select the thermistor to control room temperature.
The factory setting for the Second Code No. is "01" and room temperature is controlled by the
indoor unit suction air thermistor and remote controller thermistor.
When the Second Code No. is set to "02", room temperature is controlled by the suction air
thermistor.
When the Second Code No. is set to "03", room temperature is controlled by the remote
controller thermistor.
(4) "Filter Cleaning" Displayed or Not Displayed
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
(5) Optional Output Switching
Using this setting, "operation output signal" and "abnormal output signal" can be provided.
Output signal is output between terminals K1 and K2 of "customized wiring adapter," an optional
accessory.
Filter Specs.
Setting
Standard
Long Life
Ultra Long Life Filter
Contamination Light
200 hrs.
2,500 hrs.
10,000 hrs.
Contamination Heavy
100 hrs.
1,250 hrs.
5,000 hrs.
Mode No.
Setting Switch No.
Setting Position No.
Setting
10 (20)
1
01
Long-Life Filter
02
Ultra-Long-Life Filter (1)
03
—
Mode No.
First Code No.
Second Code No. Thermistor that controls room temperature
10 (20)
2
01
Indoor air thermistor for remote controller
and suction air thermistor for indoor unit
02
Suction air thermistor for indoor unit
03
Thermistor for remote controller
Mode No.
First Code No.
Second Code No.
"Filter Cleaning" display
10 (20)
3
01
Display
02
No display
Mode No.
First Code No.
Second Code No.
Remarks
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is
provided.
03
Output linked with "Start/Stop" of remote
controller is provided.
04
In case of "Malfunction Display" appears
on the remote controller, output is
provided.
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...