Wiring Diagrams for Reference
SiBE37-701
400
Appendix
2.2
Field Wiring
REYQ8P / 10P / 12P / 14P / 16PY1B
OUTDOOR UNITS
2 WIRES
CABLE
(TRANSMISSION LINE)
2 WIRES
CABLE
(TRANSMISSION LINE)
2 WIRES
CABLE
(PO
WER LINE)
2 WIRES
CABLE
(PO
WER LINE)
2 WIRES
CABLE
(PO
WER LINE)
2 WIRES
CABLE
(PO
WER LINE)
2 WIRES
CABLE
(PO
WER LINE)
2 WIRES
CABLE
(PO
WER LINE)
2 WIRES
CABLE
(PO
WER LINE)
2 WIRES
CABLE
(PO
WER LINE)
2 WIRES
CABLE
(TRANSMISSION LINE)
INDOOR UNITS
BS UNITS
L
MAIN
SWITCH
N
PO
WER SUPPL
Y
L
FUSE
FUSE
FUSE
PO
WER SUPPL
Y
SWITCH
N
L
SWITCH
N
L
FUSE
LN
FUSE
SWITCH
FUSE
SWITCH
N
COOLING ONL
Y UNIT
L
N
Notes 1) All wir
ing, components and mater
ials to be procured
on the site m
ust comply with the applicab
le local and
national codes
.
2) Use copper conductors only
.
3) As f
or details
, see wir
ing diag
ram.
4) Install circuit break
er f
or saf
ety
.
5) All field wir
ing and components m
ust be pro
vided b
y
licensed electr
ician.
FUSE
N
L2
SWITCH
N
SWITCH
FUSE
L1
L2
L3
N
L
L
SWITCH
L1
MAIN SWITCH
FUSE
SWITCH
N
SWITCH
N
L
L3
6) Unit shall be g
rounded in compliance with the applicab
le local and national codes
.
7) Wiring shown are general points-of-connection guides only and are not intended for or
to include all details f
or a specific installation.
8) Be sure to install the s
witch and the fuse to the po
w
er line of each equipment.
9) Install the main s
witch that can interr
upt all the po
w
er souces in an integ
rated manner
because this system consists of the equipment utilizing the m
ultiple po
w
er sources
.
10) If there e
xists the possibility of re
v
ersed phase
, lose phase
, momentar
y b
lac
k
out or the
po
w
er goes on and off while the product is oper
ating, attach a re
v
ersed phase protection
circuit locally
.
Running the product in re
v
ersed phase ma
y break the compressor and other par
ts
.
2 WIRES
CABLE
(TRANSMISSION LINE)
2 WIRES
CABLE
(TRANSMISSION LINE)
2 WIRES
CABLE
(TRANSMISSION LINE)
2 WIRES
CABLE
(TRANSMISSION LINE)
3D057764A
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...