SiBE37-701
Specifications
Specifications
37
1-1 TECHNICAL SPECIFICATIONS
FXDQ20MV3B
FXDQ25MV3B
Standard
Accessories
Standard Accessories
Installation and operation manual
Fuse
Caution for servicing sticker
Suction air filter
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 8m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 8m, level difference : 0m.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
1-2 ELECTRICAL SPECIFICATIONS
FXDQ20MV3B
FXDQ25MV3B
Power
Supply
Name
V1
Phase
1
1
Frequency
Hz
50
50
Voltage
V
230
230
Current
Minimum circuit amps
(MCA)
A
0.20
0.20
Maximum fuse amps
(MFA)
A
16.00
16.00
Full load amps (FLA)
A
0.10
0.10
Voltage
range
Minimum
V
-10%
Maximum
V
+10%
Power Supply Intake
Both indoor and outdoor unit
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 × FLA
MFA < 4 × FLA
next lower standard fuse rating minimum 16A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
Finally, click on the document title of your choice.
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...