Specifications
SiBE37-701
40
Specifications
Concealed Ceiling Unit
1-1 TECHNICAL SPECIFICATIONS
FXSQ63MV3B
FXSQ80MV3B
FXSQ100MV3B
FXSQ125MV3B
Capacity
(Conditions
specified in
1)
Cooling
kW
7.10
9.00
11.20
14.00
Heating
kW
8.00
10.00
12.50
16.00
Power input
(Nominal)
Cooling
kW
0.189
0.234
0.242
0.321
Heating
kW
0.169
0.214
0.222
0.301
Casing
Colour
Non painted
Material
Galvanised steel
Dimensions
Packing
Height
mm
354
356
356
356
Width
mm
1,192
1,596
1,596
1,596
Depth
mm
936
938
938
938
Unit
Height
mm
300
300
300
300
Width
mm
1,000
1,400
1,400
1,400
Depth
mm
800
800
800
800
Weight
Unit
kg
41
51
51
52
Packed Unit
kg
47
58
58
59
Required Ceiling Void
mm
350
350
350
350
Heat
Exchanger
Dimensions Length
mm
750
1,150
1,150
1,150
Nr of Rows
3
3
3
3
Fin Pitch
mm
1.75
1.75
1.75
1.75
Nr of Passes
7
10
10
10
Face Area
m²
0.221
0.338
0.338
0.338
Nr of Stages
14
14
14
14
Tube type
Hi-XSS (7)
Fin
Fin type
Symmetric waffle louvre
Treatment
Hydrophilic
Fan
Type
Sirocco fan
Quantity
2
3
3
3
Air Flow
Rate
Cooling
High
m³/min
21.00
27.00
28.00
38.00
Low
m³/min
15.50
20.00
20.50
28.00
Heating
High
m³/min
21.00
27.00
28.00
38.00
Low
m³/min
15.50
20.00
20.50
28.00
Fan
External
static
pressure
High
Pa
123
141
141
109
Standard
Pa
111
125
125
93
Low
Pa
98
Motor
Quantity
1
1
1
1
Model
2D18H2AB1V1
3D18H2AH1V1
3D18H2AH1V1
3D18H2AG1V1
Steps
step motor
Output
(high)
W
125
135
135
225
Drive
Direct drive
Refrigerant
Name
R-410A
Sound Level Cooling
Sound
power
(nominal)
dBA
56.0
55.0
56.0
65.0
Cooling
Sound
Pressure
High
dBA
35.0
37.0
38.0
40.0
Low
dBA
30.0
31.0
33.0
35.0
Heating
Sound
Pressure
High
dBA
35.0
37.0
38.0
40.0
Low
dBA
30.0
31.0
33.0
35.0
Piping
connections
Liquid
(OD)
Type
Flare connection
Diameter
mm
9.5
9.5
9.5
9.5
Gas
Type
Flare connection
Diameter
mm
15.9
15.9
15.9
15.9
Drain
Diameter
mm
32
32
32
32
Heat Insulation
Both liquid and gas pipes
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...