Basic Control
SiBE37-701
116
Function
2.6
Heat Exchanger Control
While in heating or cool/heat simultaneous operation, ensure target condensing and
evaporating temperature by changing over the air heat exchange of outdoor unit to the
evaporator or the condenser in response to loads.
[Single system]
[Multi outdoor unit system]
Note 1. "GR" is a numeric value
representing the current
balanced condition and
calculated from target
condensing temperature,
target evaporating
temperature, current
condensing temperature,
and current evaporating
temperature.
Outdoor unit
Left side
Condenser
Right side
Condenser
Outdoor unit
Left side
Evaporator
Right side
–
Outdoor unit
Left side
Evaporator
Right side
Evaporator
Outdoor unit
Left side
Evaporator
Right side
Condenser
GR > 25
GR < -20
GR > 25
GR < -20
GR > 15
GR < -10
GR > 15
GR < -10
A1
A2
Outdoor unit
Note 1. "GR" is a numeric value representing the current balanced
condition and calculated from target condensing temperature,
target evaporating temperature, current condensing
temperature, and current evaporating temperature.
Note 2. On the system with two outdoor units, if there is no step for the
destination of transition, that step will be skipped.
1
Condenser
2
Condenser
3
Condenser
B1
Outdoor unit
1
–
2
Evaporator
3
–
Outdoor unit
1
Condenser
2
Condenser
3
Condenser
Outdoor unit
1
Condenser
2
Condenser
3
–
Outdoor unit
1
Condenser
2
Evaporator
3
Evaporator
GR > 25
GR < -20
GR > 25
GR < -20
GR > 25
A3
GR > 15
GR < -10
B2
Outdoor unit
1
Evaporator
2
Evaporator
3
–
Outdoor unit
1
Evaporator
2
Evaporator
3
Evaporator
GR > 15
GR < -10
B3
A4
GR > 15
GR < -10
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...