Special Control
SiBE37-701
124
Function
3.4
Defrost Operation
[Start conditions]
Referring to the following conditions, start defrost operation.
• When there is a decrease in the coefficient of heat transfer of outdoor unit heat exchanger
• When there is a drop in the temperature of outdoor unit heat exchanger outlet (Tb)
• When the low pressure stays low for a certain amount of time (2 hours minimum)
Furthermore, the thermal conductivity of outdoor unit heat exchanger is calculated by Tc, Te, and compressor loads.
Defrosting outdoor unit actuator
Symbol
Elect.
symbol
Defrost operation
Operation after defrost
REYQ
REMQ
Compressor 1
—
M1C M1C REYQ8•10•12P: 232Hz+ON
REYQ14•16P: 232Hz+232Hz
REMQ8P: 210Hz
REMQ10•12P: 210Hz+ON
REMQ14•16P: 202Hz+ON+ON
REYQ8•10•12P: upper limit
124Hz(STD Holds)
REYQ14•16P: 232Hz+232Hz
REMQ8P: 210Hz
REMQ10•12P: 210Hz+ON
REMQ14•16P: 210Hz+ON+ON
Compressor 2
M2C M2C
Compressor 3
—
M3C
Outdoor unit fan 1
—
M1F M1F
Outdoor unit fan 2
M2F M2F
Four way valve (for heat changer
selection)
20SA
Y2S
Y9S
Y3S OFF
OFF
Four way valve (for high- and low-
pressure gas pipe selection)
20SB Y8S
Y2S Holds
Holds
Electronic expansion valve (main)
EVM
Y1E
Y3E
Y1E 1375pls
0pls
Electronic expansion valve
(subcooling)
EVT
Y2E
Y5E
Y3E SH control
0pls
Electronic expansion valve
(refilling refrigerant)
EVJ
Y4E
Y2E 80pls
80pls
Solenoid valve (main bypass)
SVE
Y5S
Y10S
Y6S ON
OFF
Solenoid valve (hot gas)
SVP
Y4S
Y5S OFF
OFF
Solenoid valve (liquid pipe of
refrigerant regulator)
SVL
Y3S
Y4S 0pls
0pls
Solenoid valve (gas discharge
pipe of refrigerant regulator)
SVG
Y1S
Y1S 0pls
0pls
Solenoid valve (drain pipe of
refrigerant regulator)
SVO
Y7S
Y7S 0pls
0pls
Solenoid valve (discharge pipe of
refrigerant regulator)
SVT
Y6S
Y8S 0pls
0pls
End conditions
REYP8 to 16P (by unit)
•
6 min. and 30 sec.
•
Tb > 11°C continues for a
period of 90 consecutive sec.
•
Pc_max > 3.04MP
REMQ8 to 12P (by unit)
•
5 min. and 30 sec.
•
Tb > 11°C for a period of
10 consecutive sec.
•
Pc_max > 3.04MPa
REMQ14 and16P (by unit)
•
5 min. and 30 sec.
•
Tb > 11°C for a period of 30
consecutive sec.
•
Pc_max > 3.04MPa
•
30 sec.
•
Pc_max>3.04MPa
&
Pcmax>2.45MPa
Pcmax>3.04MPa
Pcmax<2.36MPa
Pcmax<2.95MPa
FANSTEP4
FANSTEP6
OFF
Pcmax>2.45MPa
Pcmax>3.04MPa
Pcmax<2.36MPa
Pcmax<2.95MPa
FANSTEP4
FANSTEP6
OFF
or
or
or
or
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...