Test Operation
SiBE37-701
164
Test Operation
[How to Check How Many Units are Connected]
It is possible to find out how many indoor or outdoor unit in the system are turned on by
operating the push button on the PC-board (A1P) of outdoor unit (In case of multi system
master unit).
Follow the procedure below to check how many indoor or outdoor units are turned on.
Note:
Press the “MODE button” (BS1) if you get confused while operating.
This returns to
Setting Mode 1
(H1P: OFF, default).
(LED display :
h
...OFF
k
...ON
l
...Blinking
∗
...Uncertain)
LED display
H
1
P
H
2
P
H
3
P
H
4
P
H
5
P
H
6
P
H
7
P
1.
Press the MODE button (BS1) once at Setting Mode 1 (H1P: off) and set
the MONITOR MODE (H1P: Blinking).
l h h h h h h
2.
Press the SET button (BS2) the number of
times until the LED display matches that at
right.
For checking the
number of outdoor units:
eight times
l h h k h h h
For checking the
number of indoor units:
five times
l h h h k h k
3.
Press the RETURN button (BS3) and read the number of units from the
display of H2P through H7P.
[Reading Method]
The display of H2P through H7P should be read as a binary number,
with
l
standing for “1” and
h
standing for “0”.
l
∗ ∗ ∗ ∗ ∗ ∗
l h l h l l h
4.
Press the MODE button (BS1) once. This returns to
Setting Mode 1
(H1P: OFF, default).
h h k h h h h
Ex: For the LED display at right, this would be “0 1 0 1 1 0 ”,
which would mean 22 units are connected.
Note: “000000” indicates 64 units.
32 ×
0
+ 16 ×
1
+ 8 ×
0
+ 4 ×
1
+ 2 ×
1
+ 1 ×
0
= 22 units
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...