Field Setting
SiBE37-701
204
Test Operation
3.2.2 Setting by Dip Switches
(1) Factory setting of initial PC board.
Do not make any changes in all factory settings of the DIP switches on the control PC board.
*
For detail of the setting procedure, refer to information on the following pages.
While the PC board assembly is replaced, the "U3" malfunction (Test run not carried out yet)
code is displayed. In this case, carry out the test run again.
If the "PJ", "UA", or "U7" malfunction code is displayed, recheck for DIP switch settings.
After the completion of rechecking for the settings, turn ON the power supply again.
1 2 3 4
1 2 3 4
ON
OFF
ON
OFF
DS1
DS2
Status of DIP switches
: Represents the factory setting positions
of the switches.
Setting at replacement by spare PC board
Caution
DIP switch Setting after changing the main PC board(A1P) to spare parts PC board
After the replacement by the spare PC board, be sure to make settings shown below.
When you change the main PC board(A1P) to spare parts PC board, please carry out the
following setting.
DIP Switch Detail
DS No.
Item
Contents
DS1-2
Power supply
specification
ON
200V class (220V)
OFF (Factory
setting of spare
PC board)
400V class (380V)
DS1-3
Except
Multiple
use
Cooling only/Heat-
pump setting
ON
Cooling only setting
OFF (Factory
setting of spare
PC board)
Heat pump setting
DS1-4
Unit allocation
setting
ON
Make the following settings according to allocation of
unit. (All models are set to OFF at factory.)
DS2-1
OFF (Factory
setting of spare
PC board)
DS2-2
Model setting
Make the following settings according to models of outdoor units.
(All models are set to OFF at factory.)
* Refer to following pages for setting detail.
DS2-3
DS2-4
1 2 3 4
1 2 3 4
DS1
DS2
ON
OFF
ON
OFF
Initial conditions of dip switches
Multiple
use Single
use (Main)
Single use
(sab)
Domestic
Japan
Overseas
General
Europe
DS1-4
DS1-3
OFF
OFF
ON
DS2-1
DS1-4
OFF
ON
OFF
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...