Field Setting
SiBE37-701
228
Test Operation
[Cancel of Emergency Operation]
To cancel the emergency operation, conduct the following setting. (Return to Factory setting.)
<REYQ8 to 16PY1>
k
Cancel disabling the compressor 1 (on the right side) from operating:
Set No. 38 "Disable-compressor-1 operation" of setting mode 2 to "OFF".
k
Cancel disabling the compressor 2 (on the left side) from operating:
Set No. 39 "Disable-compressor-2 operation" of setting mode 2 to "OFF".
<REYQ18 to 48PY1>
Cancel the disable-operation setting by each outdoor unit.
Make the following setting on the outdoor unit 1. (If this setting is made on an outdoor unit other
than the outdoor unit 2, the setting will become invalid.)
*It is possible to tell the outdoor units 1, 2, and 3 according the LED displays shown below.
k
Cancel disabling the outdoor unit 1 from operating:
Set No. 38 "Disable outdoor unit 1 operation" of setting mode 2 to "OFF".
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step)
H1P-----------H7P
(1) Press and hold the PAGE button (BS1)
for 5 sec. or more.
k h h h h h h
(2) Press the OPERATE button (BS2) 38
times.
k k h h k k h
(3) Press the CHECK button (BS3) once.
k h h h h l h
(4) Press the OPERATE button (BS2) once.
k h h h h h l
(Factory setting)
(5) Press the CHECK button (BS3) twice.
k h h h h h h
(6) Press the PAGE button (BS1) once.
h h k h h h h
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step)
H1P-----------H7P
(1) Press the PAGE button (BS1) for 5
seconds or more.
k h h h h h h
(2) Press the OPERATE button (BS2) 39
times.
k k h h k k k
(3) Press the CHECK button (BS3) once.
k h h h h l h
(4) Press the OPERATE button (BS2) once.
k h h h h h l
(Factory setting)
(5) Press the CHECK button (BS3) twice.
k h h h h h h
(6) Press the PAGE button (BS1) once.
h h k h h h h
LED display (
k
: ON,
h
: OFF,
l
: Blink)
H1P-----------H7P H8P
Outdoor unit 1:
h h k h h h h
k
Outdoor unit 2:
h h h h h h h
l
Outdoor unit 3:
h h h h h h h
h
(Factory setting)
LED display (
k
: ON,
h
: OFF,
l
: Blink)
(Step)
H1P-----------H7P
(1) Press and hold the PAGE button (BS1)
for 5 sec. or more.
k h h h h h h
(2) Press the OPERATE button (BS2) 38
times.
k k h h k k h
(3) Press the CHECK button (BS3) once.
k h h h h l h
(4) Press the OPERATE button (BS2) once.
k h h h h h l
(Factory setting)
(5) Press the CHECK button (BS3) twice.
k h h h h h h
(6) Press the PAGE button (BS1) once.
h h k h h h h
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...