3
English
REYQ40PY1 .......................... 500
~1300
REYQ42PY1 .......................... 525
~1365
REYQ44PY1 .......................... 550
~1430
REYQ46PY1 .......................... 575
~1495
REYQ48PY1 .......................... 600
~1560
•
For installing the 2 units multi system, Outdoor unit multi connec-
tion piping kit "BHFP26A90" are required.
For installing the 3 units multi system, Outdoor unit multi connec-
tion piping kit "BHFP26A136" are required.
•
When installing the multi system, connect the units as following
order.
If install the system with different order, the Outdoor unit multi
connection piping kit may not suit and some pipe size reducer
(field supply) may be required.
•
If the total capacity of the connected indoor units exceeds the
capacity of the outdoor unit, cooling and heating performance
may drop when running the indoor units. See the capacity table in
the Engineering Data Book for details.
2-2 Standard supplied accessories
Confirm the following accessories are included. The storage location
of the accessories is shown in figure 1.
Note
Do not throw away any of the accessories until installation is com-
plete. They are needed for installation work.
(Refer to figure 1)
1.
Clamps, Manuals, etc.
2.
Accessory pipes
2-3 Option accessory
To install the outdoor units, the following optional parts are also required.
To select an optimum kit, refer to “
6. REFRIGERANT PIPING
”.
• Outdoor unit multi connection piping kit
• Refrigerant branching kit
• Pipe size reducer
Make sure that any separately purchased accessories are designed
for use with R410A.
2-4 Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of specifications.
2-5 Main components
For main components and function of the main components, refer to
the Engineering Data Book.
3.
SELECTION OF LOCATION
Select a location for installation that meets the following conditions
and get the customer’s permission.
1.
There is no danger of fire due to leakage of inflammable gas.
2.
Select the location of the unit in such a way that neither the dis-
charged air nor the sound generated by the unit disturb anyone.
3.
The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
4.
The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length.
(Refer to
“6. REFRIGERANT PIPING”
)
5.
Locations where the unit’s suction vent and outlet vent do not gen-
erally face the wind.
Wind blowing directly into the suction or outlet vents will interfere
with the unit’s operation.
If necessary, install some kind of obstruction to block the wind.
6.
The space around the unit is adequate for servicing and the min-
imum space for air inlet and air outlet is available.
(See the
“Installation Space Examples”
for the minimum space
requirements.)
Installation Space Examples
•
The installation space requirement shown in figure 2 is a refer-
ence for cooling operation when the outdoor temperature is 35°C.
If the design outdoor temperature exceeds 35°C or the heat load
exceeds maximum capacity in all the outdoor unit, take an even
large space on the intake shown in figure 2.
•
During installation, install the units using the most appropriate of
the patterns shown in figure 2 for the location in question, taking
into consideration human traffic and wind.
•
If the number of units installed is more than that shown in the pat-
tern in figure 2, install the units so there are no short circuits.
•
As regards space in front of the unit, consider the space needed
for the local refrigerant piping when installing the units.
•
If the work conditions in figure 2 do not apply, contact your dealer
or Daikin directly.
(Refer to figure 2)
1.
Front side
2.
No limit to wall height
3.
Service space of front side
4.
Service space of suction side
For Patterns 1 and 2 in figure 2 :
•
Wall height for front side – no higher than 1500 mm.
•
Wall height on the suction side – no higher than 500 mm.
•
Wall height for sides – no limit.
•
If the height is exceeded the above, calculate h1 and h2 shown
in the figure below, and add h2/2 to the service space of front
side and h1/2 to the service space of suction side.
Number of outdoor units connected
2 units
3 units
Kit name
BHFP26A90
BHFP26A136
to indoor unit
Outdoor
unit A
Outdoor
unit B
Outdoor
unit C
Outdoor unit
multi connection
piping kit
(first branch)
Outdoor unit multi
connection piping kit
(second branch)
Unit capacity
A
≥
B
≥
C
2 pcs.
Shape
Liquid side
accessory
pipe (1)
Equalizer side
accessory pipe
(1)
Equalizer side
accessory pipe
(2)
L type
accessory
joint (1)
L type
accessory
joint (2)
Liquid side
accessory
pipe (2)
Suction gas
side accessory
pipe (1)
Suction gas
side accessory
pipe (2)
HP / LP gas
side accessory
pipe (1)
HP / LP gas
side accessory
pipe (2)
1 pc.
1 pc. about each item
Clamp(1)
(Large)
1 pc.
1 pc.
1 pc.
8 pcs.
Clamp(2)
pc.
1
(Small)
8 · 10 type
14 · 16 type
Quantity
Quantity
Clamp(3)
Shape
Name
Name
Name
pcs.
2
12 type
8 · 10 type
14 · 16 type
12 type
pc.
1
Manuals, etc.
Shape
Quantity
•
Operation manual
•
Installation manual
•
Declaration of conformity (PED)
•
"REQUEST FOR THE INDICATON"
label (Installation records)
•
"ADDITIONAL REF. CHARGE" label
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
2 pcs.
2 pcs.
1 pc.
1 pc.
φ
22.2
φ
28.6
φ
22.2
φ
28.6
φ
19.1
φ
22.2
φ
22.2
φ
19.1
φ
25.4
φ
19.1
for 3 piping
REFNET header
–
KHRP25M33H KHRP25M72H KHRP25M73H
REFNET joint
KHRP25A22T KHRP25A33T KHRP25A72T KHRP25A73T
for 2 piping
REFNET header KHRP26M22H KHRP26M33H KHRP26M72H KHRP26M73H
REFNET joint
KHRP26A22T KHRP26A33T KHRP26A72T
–
for 3 piping
for 2 piping
for REFNET header KHRP25M72HP KHRP25M73HP KHRP26M73HP
for REFNET joint
KHRP25M72TP KHRP25M73TP
–
Summary of Contents for VRV III REYQ18PY1
Page 23: ...3P201178 5 EM06A072 0702 FS ...