SiBE37-701
Special Control
Function
117
3.
Special Control
3.1
Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined. To position the four way valve, the master and slave units
simultaneously start up.
3.1.1 Startup Control in Cooling Operation
Actuator
Symbol
Elect.
symbol
Control
before
startup
Startup control
REYQ
REMQ
STEP1
STEP2
Compressor 1
—
M1C
M1C
0 Hz
52 Hz+OFF+OFF
52Hz+OFF+OFF+2STEP / 20
sec.
(Until it reaches
Pc-Pe>0.39 MPa)
Compressor 2
M2C
M2C
Compressor 3
—
M3C
Outdoor unit fan 1
—
M1F
M1F
STEP4
Ta<20°C: OFF
Ta
≥
20°C: STEP4
+1step/15 sec. (When
Pc_max>2.16 MPa)
-1step/15 sec. (When
Pc_max<1.77 MPa)
Outdoor unit fan 2
M2F
M2F
Electronic expansion
valve (Main)
EVM
Y1E
Y3E
Y1E
0 pls
1375 pls
1375 pls
Electronic expansion
valve (Supercooling)
EVT
Y2E
Y5E
Y3E
0 pls
0 pls
0 pls
Electronic expansion
valve (Refrigerant
charge)
EVJ
Y4E
Y2E
80 pls
80 pls
80 pls
Four way valve
(Heat exchanger switch)
20SA
Y2S
Y9S
Y3S
OFF
OFF
OFF
Four way valve (High/low
pressure gas pipe switch)
20SB
Y8S
Y2S
ON
ON
ON
Solenoid valve (Main
bypass)
SVE
Y5S
Y10S
Y6S
OFF
ON
ON
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
liquid pipe )
SVL
Y3S
Y4S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator gas
vent pipe)
SVG
Y1S
Y1S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
exhaust pipe)
SVO
Y7S
Y7S
OFF
OFF
OFF
Solenoid valve
(Refrigerant regulator
discharge pipe)
SVT
Y6S
Y8S
OFF
OFF
OFF
Ending conditions
A lapse of
60 sec.
A lapse of 15 sec.
•
A lapse of 90 sec.
•
Pc - Pe>0.39 MPa
OR
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...