Special Control
SiBE37-701
128
Function
3.6
Standby
3.6.1
Restart Standby
Used to forcedly stop the compressor for a period of 2 minutes, in order to prevent the frequent ON/OFF of the
compressor and equalize the pressure within the refrigerant system.
3.6.2 Crankcase Heater Control
In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this mode is used to control
the crankcase heater.
Actuator
Symbol
Elect.
symbol
Operation
REYQ
REMQ
REYQ8~16P
REMQ8P
REMQ10•12P
REMQ14•16P
Compressor1
—
M1C
M1C
OFF
OFF
OFF
OFF
Compressor2
—
M2C
M2C
OFF
—
OFF
OFF
Compressor3
—
M3C
M3C
—
—
—
OFF
Outdoor unit fan1
—
MF1
MF1
Ta>30
°
C: STEP4
Ta
≤
30
°
C: OFF
Ta>30
°
C: STEP4
Ta
≤
30
°
C: OFF
Ta>30
°
C: STEP4
Ta
≤
30
°
C: OFF
Ta>30
°
C: STEP4
Ta
≤
30
°
C: OFF
Outdoor unit fan2
—
MF2
MF2
Ta>30
°
C: STEP4
Ta
≤
30
°
C: OFF
—
—
Ta>30
°
C: STEP4
Ta
≤
30
°
C: OFF
Electronic expansion valve
(Main)
EVM
Y1E
Y3E
Y1E
0 pls
Electronic expansion valve
(Supercooling)
EVT
Y2E
Y5E
Y3E
0 pls
Electronic expansion valve
(Refrigerant charge)
EVJ
Y4E
Y2E
80 pls
Four way valve (Heat
exchanger switch)
20SA
Y2S
Y9S
Y3S
Holds
Four way valve (High/low
pressure gas pipe switch)
20SB
Y8S
Y2S
Holds
Solenoid valve (Main bypass) SVE
Y5S
Y10S
Y6S
OFF
Solenoid valve (Hot gas)
SVP
Y4S
Y5S
OFF
Solenoid valve (Refrigerant
regulator liquid pipe )
SVL
Y3S
Y4S
OFF
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG
Y1S
Y1S
OFF
Solenoid valve (Refrigerant
regulator exhaust pipe)
SVO
Y7S
Y7S
OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT
Y6S
Y8S
OFF
Ending conditions
—
2 min.
Crankcase heater
OFF
Crankcase heater
ON
Discharge pipe
temperature < 70
˚C
Discharge pipe
temperature > 75
˚C
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...