Field Setting
SiBE37-701
214
Test Operation
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
24
ENECUT test
operation (Domestic
Japan only)
k
h
k
k
h
h
h
ENECUT output OFF
k h h h h h k
∗
ENECUT output forced ON
k h h h h k h
25 Low noise setting
k
h
k
k
h
h
k
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
∗
Level 3 (outdoor fan with 4 step or lower)
k h h h k h h
26
Night-time low noise
operation start
setting
k
h
k
k
h
k
h
About 20:00
k h h h h h k
About 22:00 (factory setting)
k h h h h k h
∗
About 24:00
k h h h k h h
27
Night-time low noise
operation end
setting
k
h
k
k
h
k
k
About 6:00
k h h h h h k
About 7:00
k h h h h k h
About 8:00 (factory setting)
k h h h k h h
∗
28
Power transistor
check mode
k
h
k
k
k
h
h
OFF
k h h h h h k
∗
ON
k h h h h k h
29
Capacity
precedence setting
k
h
k
k
k
h
k
OFF
k h h h h h k
∗
ON
k h h h h k h
30 Demand setting 1
k
h
k
k
k
k
h
60 % demand
k h h h h h k
70 % demand
k h h h h k h
∗
80 % demand
k h h h k h h
32
Normal demand
setting
k
k
h
h
h
h
h
OFF
k h h h h h k
∗
Demand 1
k h h h h k h
Demand 2
k h h h k h h
38
Emergency
operation
(Master unit is
inhibited to operate.)
k
k
h
h
k
k
h
OFF
k h h h h h k
∗
Master unit operation: Inhibited
k h h h h k h
39
Emergency
operation
(Slave unit 1 is
inhibited to operate.)
k
k
h
h
k
k
k
OFF
k h h h h h k
∗
Slave unit 1 operation: Inhibited
k h h h h k h
40
Emergency
operation
(Slave unit 2 is
inhibited to operate.)
k
k
h
k
h
h
h
OFF
k h h h h h k
∗
Slave unit 2 operation: Inhibited
k h h h h k h
41
Prevention of minute
heating operation by
heating thermostat
OFF unit or non-
heating-operation
unit
k
k
h
k
h
h
k
OFF
k h h h h h h
Non-heating-operation unit
k h h h h h k
Heating thermostat OFF unit
k h h h h k h
Non-heating-ope Thermostat OFF unit
k h h h h k k
∗
42
Setting of BS Cool-
Heat selection
control time
k
k
h
k
h
k
h
6 min.
k h h h h h h
∗
4 min.
k h h h h h k
51
Master-slave set-up
for multi outdoor
units
k
k
k
h
h
k
k
Automatic judgment
k h h h h h h
∗
Master
k h h h h h k
Slave 1
k h h h h k h
Slave 2
k h h h h k k
The numbers in the "No." column represent the number of times to press the SET (BS2) button.
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...