Troubleshooting by Indication on the Remote Controller
Troubleshooting
293
3.25
“
J2
”
Outdoor Unit: Current Sensor Malfunction
Remote
Controller
Display
J2
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected according to the current value detected by current sensor.
Malfunction
Decision
Conditions
When the current value detected by current sensor becomes 5A or lower, or 40A or more during
standard compressor operation.
Supposed
Causes
Faulty current sensor (A6P, A8P)
Faulty outdoor unit PC board
Defective compressor
Troubleshooting
(V3071)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
current sensor
mounted on the T-phase
(A6P) and R-phase
(A8P) wire?
Are the
current sensors inversely
connected to two STD
compressors?
Is the
connector for
current sensor
connected to X25A, X26A
on outdoor unit
PC board
(A1P)?
Replace current sensor or outdoor
unit PC board.
Connect the connector, and
operate unit again.
NO
NO
Mount the current sensor
correctly, and operate unit again.
YES
Correct the connections between
the current sensors and the STD
compressors.
Applicable
compressor coil wire is
broken.
YES
Replace compressor.
NO
NO
YES
YES
Check the current sensor corresponding to the malfunction
code “
J2
” in the monitor mode.
(Refer to P248~249 for how to check)
Check 4 shows as follows:
→
Current sensor for constant rate compressor 1
Check 4 shows as follows:
→
Current sensor for constant rate compressor 2
Explanation for “ ”
Master unit
Slave unit 1
Slave unit 2
System
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...