Troubleshooting (OP: Unified ON/OFF Controller)
SiBE37-701
368
Troubleshooting
5.3
Display “Under Centralized Control” Blinks (Repeats
Double Blink)
Remote
Controller
Display
“under centralized control” (Repeats double blink)
Applicable
Models
Unified ON/OFF controller
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
When no central control addresses are set to indoor units.
When no indoor units are connected within the control range.
Supposed
Causes
Central control address (group No.) is not set for indoor unit.
Improper control range setting switch
Improper wiring of transmission wiring
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2844)
Is the control
range setting switch
set correctly?
Is
the transmission
wiring disconnected or
wired incorrectly?
Replace the unified ON/OFF
controller.
Fix the wiring correctly.
Set by remote controller the
central control address for all
indoor units connected to the
central control line.
YES
YES
Set the control range setting
switch correctly and
simultaneously reset the power
supply for all optional controllers
NO
NO
NO
YES
Is the central
control address (group No.)
set for the
indoor unit?
Summary of Contents for VRV III REYQ8PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3...
Page 447: ...Example of connection SiBE37 701 436 Appendix...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix...
Page 467: ...SiBE37 701 iv Index...